ENVIRONMENTAL SYSTEMS ITRANSMISSION · INFILTRATION · GAINS · DEGREE DAYS

CHAPTER 08

Building heat balance.

A building is a thermal system with heat inputs and outputs. Adding up the U-values of Chapter 07, the air that leaks through the envelope, the heat of people and equipment and the sun through the windows gives the heating power a building needs, and, with degree days, its heating energy over a season.

Steady state throughout; metric units; equations 8.1–8.8. The weather is the Ithaca TMYx file of Chapter 01, the irradiance on windows comes from Chapter 05. US (ASHRAE) and German (DIN V 4108-6, VDI 3807) conventions are given side by side.

Start
00

ISO 52016 · ASHRAE · DIN V 4108-6

Quantities and symbols

The symbols of Chapter 07 (Q, Φ, q, θ, U) continue. Four new quantities describe a whole building.

Symbols added in Chapter 08
SymbolQuantityGermanUnitEq.
HT, HV, HTransmission, ventilation and total heat loss coefficientspezifischer Transmissions-, LüftungswärmeverlustW/K8.1–8.3
nAir change rate (ACH)Luftwechselzahlh⁻¹8.3
Φi, Φs, ΦhInternal gains, solar gains, heating powerinterne, solare Wärmegewinne, HeizleistungW8.1, 8.4
SHGC · gSolar heat gain coefficient · total solar energy transmittanceGesamtenergiedurchlassgrad g–8.4
HDD · GtHeating degree daysGradtagzahlK·d8.5–8.6
θbBalance-point temperatureHeizgrenztemperatur°C8.7
ηUtilization factor of the gainsAusnutzungsgrad–8.8
01

GAINS = LOSSES · EQ. 8.1

The energy balance of a building

Indoors stays at a constant temperature only if what comes in equals what goes out. In winter the sun and the occupants supply part of the heat; the heating supplies the rest. In summer the balance runs the other way, and the surplus must be removed by ventilation or cooling.

Heat flows that set the indoor temperature of a buildingwindow (south)Φ_T transmission (conduction): Σ U·A · (θi − θe)Φ_V infiltration,ventilationair out: ρ·c·n·V/3600 · (θi − θe)Φ_s solar: A·SHGC·GΦ_i internal: people, lights, equipmentΦ_h heatingSteady balance (heating season): Φ_h + Φ_i + Φ_s = Φ_T + Φ_V = (H_T + H_V) · (θi − θe)
Figure 1. Heat flows of a buildingEditable SVG ↓
steady heat balance in the heating seasonΦh+Φi+Φs=ΦT+ΦV=(HT+HV)·(θi−θe)lecture: Qi + Qs = Qv + Qc W(8.1)
02

Σ U·A + Σ ψ·l · EQ. 8.2

Transmission

Each element of the envelope conducts U·A watts per kelvin. Thermal bridges add their linear and point values (Chapter 07, section 07).

transmission heat loss coefficientHT=∑jUj·Aj+∑kψk·lk+∑mχmW/K(8.2)
The house in Ithaca (lecture frames 616–619): transmission
ElementConstructionA m²U W/(m²K)U·A W/K
RoofTimber rafters, 220 mm cellulose, wood-fiber board1060.19220.4
Walls240 mm solid brick, 160 mm wood-fiber insulation, plaster1400.23332.6
WindowsDouble clear glazing (center of glass)242.7265.3
FloorTreated as adiabatic in the lecture70––
HT270118.3
03

ACH · BLOWER DOOR · EQ. 8.3

Infiltration and ventilation

Every cubic meter of cold air that replaces warm indoor air must be heated. Infiltration is unwanted air leakage through cracks and joints, driven by wind and buoyancy; ventilation is the fresh air the occupants need. Both are counted the same way.

Drivers of infiltration: wind and stack effect, and the blower-door testneutral pressure planeSTACK EFFECT (winter)warm air leaves at the topcold air entersat the bottomWIND: + pressure windward− suction leewardBLOWER DOOR: a fan holds 50 Pa;the air flow gives n50 (ACH at 50 Pa)Leaky building: 1–2 ACH · tight: 0.2–0.3 ACH (natural conditions). Each air change costs ρ·c·V·(θi − θe).
Figure 2. Infiltration: wind, stack effect and the blower-door testEditable SVG ↓
ventilation heat loss coefficient for an air change rate n (h⁻¹) in a volume VHV=ρ·c·n·V3600≈0.33·n·Vρ = 1.2 kg/m³, c = 1000 J/(kg·K); German texts use 0.34 (air at 20 °C) W/K(8.3)
ExampleThe house in Ithaca: V = 420 m³, n = 1 h⁻¹ (lecture frames 654–656)
HV1.2 × 1000 × 1 × 420 / 3600140 W/K
compareHT of the whole envelope118 W/K
Air change rate n · ACH
Volume of air exchanged per hour divided by the room volume. Leaky existing buildings: 1–2 h⁻¹; tight new buildings: 0.2–0.3 h⁻¹ of infiltration (lecture frame 652). Hygienic fresh-air demand is about 25–30 m³/h per person, roughly 0.3–0.5 h⁻¹ in dwellings.
Blower-door test · n50
A fan holds the building at 50 Pa and measures the air flow (ISO 9972, ASTM E779). Requirements: Germany (GEG, DIN 4108-7) n50 ≤ 3.0 h⁻¹, or ≤ 1.5 h⁻¹ with a ventilation system; IECC in the US: ≤ 3 ACH50 in climate zones 3–8 (Ithaca: 6A); Passivhaus ≤ 0.6 h⁻¹. Under natural conditions roughly n ≈ n50 / 20.
Heat recovery
A balanced mechanical ventilation system with a heat exchanger returns 75–90 % of the heat of the exhaust air: HV × (1 − ηHR). Opening windows cannot.

Airtightness and ventilation are separate tasks: "build tight, ventilate right". Do not reduce the fresh air for hygiene and moisture to save heat (Lehrbuch der Bauphysik II 4.3); reduce the leakage and recover the heat instead.

04

PEOPLE · LIGHTS · EQUIPMENT

Internal gains

People, lights and appliances turn almost all the energy they use into heat inside the building. In winter this offsets heating; in offices and schools it is often the largest cooling load.

Typical internal gains (lecture frames 658–661; ASHRAE Handbook – Fundamentals Ch. 9 and 18; SIA 2024)
SourceValueNotes
Person, seated, 1 met≈ 100–110 W total1 met = 58 W/m² × 1.8 m² body surface; about 70 W sensible, the rest latent (moisture)
Person, walking, 2 met≈ 210 Wdancing 2.4–4.4 met: the party problem of section 07
Lighting, LED office5–10 W/m²older fluorescent 10–15 W/m²
Equipment, dwelling / office2 / 7 W/m²average over the day (SIA 2024); peaks are much higher
Kettle · microwave · refrigerator1800 · 1300 · 150–600 Wwhile running; kettles also release ≈ 500 W of latent heat
Occupancy density48 m²/person bedroom · 17 m²/person officeschedules turn densities into hourly gains (SIA 2024)
05

U · SHGC (g) · LOW-E · EQ. 8.4

Windows: heat loss and solar gain

A window loses heat like a wall, only five to twenty times faster, and it lets the sun in. Two numbers describe it: the U-value for conduction, convection and long-wave radiation, and the solar heat gain coefficient for short-wave radiation.

Solar heat gain coefficient (g-value) and heat loss of double glazinglow-e on #3#4#3#2#1INSIDEOUTSIDEgas fillU_g · (θi − θe) heat lossG incident (100 %)ρ·G reflectedτ·G transmitted (short-wave)q_i absorbed, then releasedinward by convection andlong-wave radiationq_e released outwardSHGC (US, NFRC) ≈ g-value (EN 410, Gesamtenergiedurchlassgrad) = (τ·G + q_i) / G.Low-e on #2: low SHGC for cooling-dominated buildings. Low-e on #3: high SHGC for passive solar heating.U_g covers conduction, convection and long-wave radiation across the gap: the coating cuts the radiation, argon the conduction.
Figure 3. Solar heat gain coefficient (g-value) of double glazingEditable SVG ↓
solar heat gain through glazing of area A with irradiance G on its plane (Chapter 05, Eq. 30)Φs=A·SHGC·GGermany: A · g · FF · FS · FC · FW · Is, with reductions for frame, shading, sun protection and non-normal incidence (Bauphysik Gl. 5.4) W(8.4)
Glazing of the lecture (frame 669), center of glass, without frame
GlazingUg W/(m²K)SHGC (g)τvis
Single, clear 3 mm5.890.910.91
Double, clear, 6 mm air2.720.760.81
Double low-e, tinted, coating on #21.490.370.44
Double low-e, coating on #31.510.650.77
Triple low-e0.790.470.66
Whole window Uw
Uw = (Ug·Ag + Uf·Af + ψg·lg) / Aw (ISO 10077-1; Bauphysik Gl. 5.2). Frames: timber and PVC about 1.0–1.5, aluminum without a thermal break up to 4–6 W/(m²K); the spacer at the glass edge adds ψg ≈ 0.03–0.08 W/(m·K). US ratings (NFRC) give the whole-window U-factor and SHGC directly.
SHGC and g
Both are the share of incident solar radiation that ends up as heat in the room: transmitted plus the absorbed part released inward. The EN 410 g-value is usually quoted for the glass at normal incidence; NFRC SHGC for the whole window. Both fall at large angles of incidence (lecture frame 673).
Low-e coatings
A thin metal-oxide layer with ε ≈ 0.02–0.1 cuts the radiation across the gap (Chapter 07, Eq. 7.10). Argon or krypton reduce conduction. On surface #2 a selective coating also rejects solar infrared: low SHGC for cooling. On #3 it keeps a high SHGC for passive solar heating.

Is a window a heat loss or a heater? Over a heating season the answer depends on orientation and glazing. The drawing compares the conduction loss of 1 m² of glass with its solar gain for each month of the Ithaca file.

WINDOW BALANCE · ITHACA TMYx · EQ. 7.8, 8.4

PER m² OF GLASS, WITH CURRENT VALUES

Ithaca TMYx · net balance Oct–Apr (gain − loss), kWh per m² of glass, θi = 20 °C, unshaded
GlazingUgSHGCSouthEastWestNorth
06

HDD · Gt20/15 · EQ. 8.5–8.6

Degree days and seasonal heating demand

In steady state the heat loss is H × Δθ. Over a season Δθ changes every hour, but because the balance is linear we only need its sum: how much, and for how long, the outdoor temperature stayed below a base temperature. That sum is the degree-day number.

Degree hours and degree days below a base temperature0510152025Day 1Day 2Day 3°Cbase temperature 18 °Cmean 12.3 °C → 5.7 K·dmean 6.4 °C → 11.6 K·dmean 9.8 °C → 8.2 K·dShaded: degree hours, Σ (θ_base − θ_e) over the hours below the base. Divided by 24 they approach the degree days,Σ (θ_base − θ_e,mean) over the days, which use the daily mean temperature.
Figure 4. Degree hours and degree daysEditable SVG ↓
heating degree days from daily mean temperatures, and degree hours from hourly onesHDD=∑days(θbase−θe,mean)+,DH=∑hours(θbase−θe)+( )⁺: only positive values count K·d, K·h(8.5)
seasonal heat loss from the heat loss coefficientQ=H·HDD·24 h/dW/K × K·d × 24 h/d = Wh; divide by 1000 for kWh(8.6)
DEGREE DAYS · ITHACA TMYx · EQ. 8.5

EQ. 8.5 WITH CURRENT VALUES

Degree-day conventions · values for the bundled Ithaca TMYx file
ConventionDefinitionIthaca TMYxUsed for
US HDD, 65 °F (ASHRAE, NOAA)Σ (18.3 − θe,mean)⁺ over all days3568 K·denergy statistics, utilities, codes (climate zones)
Base 18 °C (lecture)Σ (18 − θe,mean)⁺3484 K·dthe lecture example
Germany Gt20/15 (VDI 3807)Σ (20 − θe,mean) over days with θe,mean < 15 °C3881 K·d · 234 daysweather correction of metered consumption, energy certificates
Germany, reference climate (DIN V 4108-6)Heating period of 185 days– (Germany: 2900 K·d)the simplified EnEV method below
07

WORKED EXAMPLE · PARTY PLANNING · EQ. 8.7–8.8

The house in Ithaca

The lecture house combines every flow of this chapter. Its transmission (section 02) and infiltration (section 03) give H; the outdoor temperature gives the heating power, the degree days its energy. The party problem asks the balance backwards: how many guests replace the heating?

HHT + HV = 118.3 + 140.0258.3 W/K

Seasonallecture, 4150 K·d: roof 2027 + walls 3248 + windows 6501 + infiltration 13,944 kWh25,720 kWh
SeasonalIthaca TMYx, 3484 K·d at 18 °C: 258.3 × 3484 × 24 / 100021,600 kWh

Party, step 1transmission at Δθ = 20 K: (20.4 + 32.6 + 65.3) × 202365 W
step 2infiltration: 140 × 202800 W
step 3existing gains: residents 1.4 × 100 W + equipment 2 W/m² × 70 m²280 W
step 4(2365 + 2800 − 280) / 100 W per guest = 48.949 guests

The gains present most of the time lower the temperature at which heating must start:

balance-point temperature (Heizgrenztemperatur)θb=θi−Φi+ΦsHthe lecture house: 20 − 280 / 258.3 = 18.9 °C; with H = 60 W/K the same gains give 15.3 °C °C(8.7)
HEAT BALANCE OF THE HOUSE · EQ. 8.1–8.7

EQ. 8.1–8.7 WITH CURRENT VALUES

Roof 106 m², walls 140 m², windows 24 m², floor 70 m² (adiabatic), volume 420 m³. Seasonal demand uses the degree days of the Ithaca file at the balance point of the residents' gains, without solar gains.

Useful gains and thermal mass

On mild, sunny days the gains exceed the losses and the surplus overheats the rooms instead of saving heating. Monthly methods (ISO 13790, DIN V 4108-6, DIN V 18599) multiply the gains by a utilization factor that depends on the gain-to-loss ratio γ and on the building's time constant τ = C/H (Chapter 07, Eq. 7.13):

utilization factor of the gainsη=1−γa1−γa+1,γ=Qi+QsQT+QV,a=1+τ16 hQh = QT + QV − η · (Qi + Qs) (Bauphysik Gl. 10.34–10.40)(8.8)
08

7 QUESTIONS · CALCULATION AND CONCEPT

Self-test

"New values" generates a new variant of a calculation. Each answer shows a worked solution.

EDITABLE VECTOR FILES

Figure files

Editable SVG files of every figure. Interactive drawings save their current state with "Save SVG".

  1. energy-flows.svg · Fig. 1 · Heat flows of a building
  2. infiltration.svg · Fig. 2 · Infiltration: wind, stack effect and the blower-door test
  3. glazing-shgc.svg · Fig. 3 · Solar heat gain coefficient (g-value) of double glazing
  4. degree-days.svg · Fig. 4 · Degree hours and degree days

SOURCES

Sources and model notes

  1. H.-M. Fischer, R. Jenisch, M. Stohrer et al., Lehrbuch der Bauphysik, 6th ed., Vieweg+Teubner, 2008. Part II Wärme: §4 (ventilation), §5.4 (windows), §10–11 (building heat demand, EnEV, DIN V 18599).0.34 · n · V, Uw, g-value and reduction factors, Gradtagzahl, Heizgrenztemperatur, utilization factor (Eq. 8.8).
  2. T. L. Bergman, A. S. Lavine, F. P. Incropera, D. P. DeWitt, Fundamentals of Heat and Mass Transfer, 6th ed., Wiley, 2007. §1.3 (conservation of energy), §12.5 (transmissivity), §13.2 (radiation exchange).Energy balance of a control volume; glazing and low-e physics.
  3. ASHRAE, Handbook — Fundamentals, SI edition: Ch. 9 (thermal comfort, metabolic rates), Ch. 14 (climatic design information, degree days), Ch. 15 (fenestration), Ch. 16 (ventilation and infiltration), Ch. 18 (load calculations).US conventions, HDD 65 °F, SHGC, internal gains.
  4. EN ISO 13790:2008 / EN ISO 52016-1:2017; DIN V 4108-6; DIN V 18599; VDI 3807-1.Monthly and hourly methods, utilization factor, heat capacity classes, Gt20/15.
  5. EN ISO 10077-1 (window Uw), EN 410 (g-value), NFRC 100/200 (U-factor, SHGC), EN ISO 9972 and ASTM E779 (blower door), EN ISO 13370 (ground).Section 02–05.
  6. S. V. Szokolay, Introduction to Architectural Science, 3rd ed., Routledge, 2014. §1.4 (heat flow, degree days); N. Lechner, Heating, Cooling, Lighting, 4th ed., Wiley, 2015.Degree-day method and the limits of cooling degree days.
  7. SIA Merkblatt 2024, Raumnutzungsdaten für Energie- und Gebäudetechnik.Occupancy densities and equipment gains.
  8. Ithaca Tompkins Rgnl AP TMYx (2009–2023), climate.onebuilding.org ↗Degree days and window balances; the dataset of Chapter 01.
  9. T. Dogan, ES1 lecture "Heat transfer, insulation materials", Cornell AAP, 2026, frames 583–684.Order of topics, the house in Ithaca and the party problem.
Model assumptions and precision

Steady state, one well-mixed zone at θi. Degree days use daily means of the 24 hourly values of the TMYx file. Window balances use center-of-glass U and SHGC, a vertical unshaded window, the isotropic sky of Chapter 05 with ground reflectance 0.2, and no angle dependence of the SHGC; gains are not reduced by a utilization factor. The house lab treats the floor as adiabatic, as in the lecture, and counts 100 W per person (sensible plus latent); seasonal demand uses the degree days at the balance point of the residents' and equipment gains and omits solar gains.