Course reader
ENVIRONMENTAL SYSTEMS ICONDUCTION · CONVECTION · RADIATION · U-VALUE · STEADY STATE

CHAPTER 07

Heat transfer through the envelope.

How heat moves through walls, roofs and windows, and how a few layers of material decide how much energy a building needs and how warm its surfaces feel. The chapter stays with steady state: temperatures that do not change with time. Section 09 explains when that is not good enough.

All units are metric (SI). Symbols follow ISO 7345 and ISO 6946, as used in DIN 4108 and the Lehrbuch der Bauphysik; the US terms of ASHRAE and Incropera are listed beside them. Equations are numbered 7.1–7.13. Chapter 08 adds the flows up to a building heat balance.

Start
00

ISO 7345 · ENGLISH AND GERMAN TERMS

Quantities and symbols

Building physics in Germany and in the US uses the same physics with different words and letters. This reader uses the ISO symbols. Keep three quantities apart: energy Q, a flow of energy per time Φ, and that flow per area q.

Symbols used in Chapters 07 and 08
SymbolQuantityGerman (DIN)UnitAlso written
QHeat, energyWärmemengeJ, kWhE (lecture)
ΦHeat flow rateWärmestromW = J/sQ (lecture, Szokolay), q (Incropera), Q̇
qHeat flux, heat flow densityWärmestromdichteW/m²q″ (Incropera)
θ, TTemperature (Celsius, kelvin)Temperatur°C, KT in °C (lecture), t (ASHRAE)
λThermal conductivityWärmeleitfähigkeitW/(m·K)k (Incropera, ASHRAE)
dThicknessDickemb (Szokolay), L (Incropera)
RThermal resistance of a layerWärmedurchlasswiderstandm²K/WRSI; US labels use ft²·°F·h/Btu
hc, hrConvective, radiative heat transfer coefficientWärmeübergangskoeffizientW/(m²K)α (older German texts)
Rsi, RseInside, outside surface resistanceWärmeübergangswiderstandm²K/Wsurface film (ASHRAE)
RTTotal thermal resistance, air to airWärmedurchgangswiderstandm²K/WR-value of the assembly
UThermal transmittanceWärmedurchgangskoeffizientW/(m²K)k (older German texts), U-factor
c, ρSpecific heat capacity, densityspezifische Wärmekapazität, RohdichteJ/(kg·K), kg/m³cp
εEmissivity (long-wave)Emissionsgrad–
ψ, χLinear, point thermal transmittance (thermal bridges)längen-, punktbezogener WärmedurchgangskoeffizientW/(m·K), W/K
fRsiTemperature factor of the inside surfaceTemperaturfaktor–
α (a), bThermal diffusivity, thermal effusivityTemperaturleitfähigkeit a, Wärmeeindringkoeffizient bm²/s, J/(m²K·s½)α (Incropera)
US LABELS

Product labels in the US give R-values in imperial units. Convert once and work in SI: RSI = RIP / 5.678 and USI = UIP × 5.678. An R-13 batt is 2.29 m²K/W; R-30 is 5.28 m²K/W. In Germany λ and U are given directly, for example λ = 0.035 W/(m·K) (formerly "WLG 035").

01

ENERGY · TEMPERATURE · EQ. 7.1

Heat, temperature and specific heat

Heat is energy in transit: molecular motion in matter, or electromagnetic radiation in space. Temperature is its symptom. Heat flows by itself only from higher to lower temperature, as water flows downhill.

Energy Q · J, kWh
1 J = 1 W·s. 1 kWh = 1000 W × 3600 s = 3.6 MJ. Heating fuel and electricity are billed in kWh (Btu in the US: 1 Btu = 1055 J = 0.293 Wh).
Power, heat flow rate Φ · W
Energy per time, 1 W = 1 J/s. A heater, a person (≈ 100 W) and a wall losing heat are all described by Φ.
Temperature θ · °C, T · K
Celsius: water freezes at 0 °C and boils at 100 °C at sea level. Kelvin starts at absolute zero: T = θ + 273.15. A temperature difference is written in K: 40 °C − 10 °C = 30 K. Radiation laws need T in K.
Specific heat c · J/(kg·K)
The heat needed to warm 1 kg by 1 K. Metals 400–900, masonry and concrete 800–1000, timber 1300–2100, air 1000, water 4180 J/(kg·K), the highest of all common substances.
sensible heat to change the temperature of a massQ=m·c·ΔθJ(7.1)
Example0.5 kg of water at 20 °C in an 800 W kettle (efficiency 1.0): how long to boil?
Qm · c · Δθ = 0.5 × 4176 × (100 − 20)167,040 J
tQ / Φ = 167,040 J / 800 W209 s ≈ 3.5 min
02

CONDUCTION · CONVECTION · RADIATION

Three modes of heat transfer

Heat crosses a wall in three ways. Conduction carries it through solids and still fluids. Convection carries it between a surface and moving air. Radiation exchanges it between surfaces that see each other, with no medium needed.

Conduction, convection and radiation in a wall sectionWinter · inside θi = 20 °C (left) · outside θe = 0 °C (right)plaster · masonry · insulationCONDUCTIONq = λ · Δθ / dFREE CONVECTIONAir cools at the cold surfaceand sinks (downdraught).h_c ≈ 2.5 W/(m²K)LONG-WAVE RADIATION between room surfaces · h_r ≈ 5 W/(m²K)room surfacesFORCED CONVECTIONWind along the facadeh_c ≈ 4 + 4·v W/(m²K)≈ 20 W/(m²K) at 4 m/sRADIATION to the skyand the surroundingsSOLAR (short-wave): α · G absorbed
Figure 1. Conduction, convection and radiation in a wall sectionEditable SVG ↓
What controls each mode in a building (lecture frame 590)
ModeDriven byDesign leversRate equation
ConductionTemperature gradient in a materialInsulation thickness, conductivity λ, continuity (thermal bridges)Eq. 7.2–7.3
ConvectionSurface-to-air temperature difference, air speedExposure to wind, air gaps and their width, airtightnessEq. 7.4
RadiationDifference of T⁴ between surfacesEmissivity ε (low-e coatings, foils), solar absorptance (color), view to the skyEq. 7.5
STEADY STATE

In this chapter temperatures on both sides are held constant until nothing changes any more. Then the heat flowing into each layer equals the heat flowing out of it, and the same q passes every layer. Only the conductivity λ and thickness d matter; density and heat capacity drop out. This is the basis of U-values, design heat loads and seasonal energy estimates.

03

FOURIER · CONDUCTIVITY · RESISTANCE · EQ. 7.2–7.3

Conduction

In a solid, energy spreads from more to less agitated molecules (and, in metals, by free electrons). Through a flat layer in steady state the temperature falls linearly, and the flux is proportional to the temperature difference and inversely proportional to the thickness.

Fourier's law for a plane layer between surface temperatures θ1 > θ2q=λ·θ1−θ2dgeneral form q = −λ · dθ/dx W/m²(7.2)

The conductivity λ is the flux through a layer 1 m thick with 1 K across it, W/m² × m / K = W/(m·K). Its inverse, scaled by the thickness, is the layer's thermal resistance:

thermal resistance of a layer (Wärmedurchlasswiderstand)R=dλm²K/Wq=ΔθR,Φ=A·ΔθRresistances in series add: R = R1 + R2 + …(7.3)
Example200 mm of mineral wool (λ = 0.032) or of basalt (λ = 3.5), 1 m², Δθ = 10 K between the surfaces (lecture frames 597–600)
Rwool0.2 / 0.0326.25 m²K/W
Φwool1 m² × 10 K / 6.251.6 W
Rbasalt0.2 / 3.50.057 m²K/W
Φbasalt1 m² × 10 K / 0.057175 W
Both50 mm wool + 200 mm basalt: R = 1.56 + 0.057 = 1.62 → Φ = 10 / 1.626.2 W
Typical properties of building materials at about 20 °C
Materialλ W/(m·K)ρ kg/m³c J/(kg·K)R of 100 mm, m²K/W
Steel50–6078504500.002
Basalt, granite2.8–3.52650–2850775–10000.03
Concrete, normal weight1.4–2.02300–2400880–10000.06
Glass1.025007500.10
Brick, common0.7–0.81800–1920835–10000.14
Aerated concrete (AAC) masonry0.08–0.24300–70010000.4–1.25
Gypsum board0.17–0.25700–9001000–10900.5
Hardwood / softwood, across the grain0.16 / 0.12720 / 5101255–21000.6 / 0.8
Insulation (section 08)0.02–0.0515–200800–21002–5
Still air0.0261.21000(convection, section 06)
04

NEWTON · STEFAN–BOLTZMANN · ISO 6946 · EQ. 7.4–7.6

Convection and radiation at surfaces

The air next to a wall does not take the surface temperature at once: a thin boundary layer separates them. Convection and long-wave radiation act in parallel across it, and together they form the surface resistance.

convection (Newton's law of cooling)q=hc·(θs−θair)hc is not a material property: it depends on air speed, surface direction and roughness(7.4)
Convection coefficient hc in air, W/(m²K)
SituationhcSource
Free convection (buoyancy)2–25 (Incropera) · 3–10 (Bauphysik)Incropera Table 1.1; Bauphysik Tafel 1.5
Forced convection (wind, fans)25–250 · 10–100as above
Room surface: up / horizontal / down5.0 / 2.5 / 0.7ISO 6946 Annex C
Outside surface, wind speed v in m/s4 + 4·v (≈ 20 at 4 m/s)ISO 6946 Annex C

Every surface emits long-wave radiation in proportion to the fourth power of its absolute temperature. Between a surface and large surroundings the net exchange is

long-wave radiation, gray surface in large surroundingsq=ε·σ·(Ts4−Tsur4)≈hr·(θs−θsur)σ = 5.67 × 10⁻⁸ W/(m²K⁴), T in Khr=ε·4σTm3≈ 5.7 ε at 20 °C, ≈ 5.1 ε at 10 °C W/(m²K)(7.5)
surface resistance: convection and radiation in parallelRs=1hc+hrinside: 1 / (2.5 + 0.9 × 5.7) = 0.13 · outside: 1 / (20 + 0.9 × 5.1) = 0.04 m²K/W(7.6)
SURFACE RESISTANCE · EQ. 7.4–7.6

EQ. 7.6 WITH CURRENT VALUES

Conventional surface resistances, m²K/W (ISO 6946, DIN EN ISO 6946)
Heat flowElementRsiRse
Horizontal (±30°)Walls, windows0.130.04
UpwardRoofs, ceilings in winter0.100.04
DownwardFloors over outside air0.170.04
05

U-VALUE · TEMPERATURE PROFILE · MOLD · EQ. 7.7–7.9

U-value and the temperature profile

From room air to outside air the heat passes the inside surface, each layer and the outside surface in series. Their resistances add. The U-value is the inverse of the total: the heat flow through 1 m² for 1 K between the air on both sides.

Wall section, temperature profile and the equivalent series resistor networkLecture example · Δθ = 10 K · the temperature drops in proportion to each resistance10100 mm · λ 0.032250 mm · λ 3.5θi = 20 °Cθe = 10 °Cθsi = 19.61 °C10.33 °Cθse = 10.12 °C1/h_c1/h_rR_si0.130 m²K/WR_1 plaster0.010 m²K/WR_2 wool3.125 m²K/WR_3 basalt0.071 m²K/W1/h_c1/h_rR_se0.040 m²K/Wθi 20.00θsi 19.61θ1 19.59θ2 10.33θse 10.12θe 10.00q = Δθ / R_T = 10 / 3.38 = 2.96 W/m² · U = 1 / R_T = 0.296 W/(m²K)
Figure 2. Temperature profile and the equivalent resistor network (lecture example)Editable SVG ↓
total resistance and thermal transmittanceRT=Rsi+∑j=1ndjλj+Rse,U=1RTm²K/W, W/(m²K)(7.7)
heat flow through an element of area A, and the energy over a time tΦ=U·A·(θi−θe),Q=Φ·tW, J(7.8)

Because the same q passes every layer, each layer takes a share of the temperature difference equal to its share of the resistance. Starting from the inside air:

temperature at the inside surface and at each interfaceθsi=θi−Rsi·q,θj=θj−1−Rj·qq = (θi − θe) / RT(7.9)
ExampleLecture wall (frames 609–610): 10 mm plaster λ 1.0, 100 mm mineral wool λ 0.032, 250 mm basalt λ 3.5; 1 m², θi = 20 °C, θe = 10 °C, for 1 hour
RT0.13 + 0.01/1.0 + 0.1/0.032 + 0.25/3.5 + 0.04 = 0.13 + 0.010 + 3.125 + 0.071 + 0.043.38 m²K/W
U1 / 3.380.296 W/(m²K)
Φ0.296 × 1 × 102.96 W
Q2.96 W × 3600 s10.7 kJ
θsi20 − 0.13 × 2.96: the wool takes 9.3 K of the 10 K19.6 °C
LAYERED CONSTRUCTION · EQ. 7.7–7.9

EQ. 7.7–7.9 WITH CURRENT VALUES

Plotted against thermal resistance (choose the axis below the drawing) the profile becomes a single straight line: the graphical method of the Lehrbuch der Bauphysik, Bild 2.11.

Why the inside surface temperature matters

06

CAVITIES · LOW-E FOIL · EQ. 7.10

Air layers

Still air is an excellent insulator (λ = 0.026 W/(m·K)), but an air layer is not 'still air'. Beyond about 15–20 mm a convection cell forms, and radiation crosses the gap regardless of its width. The resistance of a cavity therefore stops growing at about 0.18 m²K/W.

Heat transfer across a vertical air layer: conduction, convection and radiationa · 10 mmR_g = 0.15 m²K/Wwarmcoldb · 50 mmR_g = 0.18 m²K/Wwarmcoldc · 50 mm, foil ε = 0.05R_g = 0.66 m²K/Wwarmcoldconduction through still airconvection cell (rises warm, falls cold)long-wave radiation
Figure 3. Air layers: conduction, convection cell and radiationEditable SVG ↓
unventilated air layer between two large parallel surfaces (ISO 6946 Annex D)Rg=1ha+E·hr0,E=11/ε1+1/ε2−1ha: conduction (0.025/d) or convection, whichever is larger; E: exchange factor (Incropera Eq. 13.19; Bauphysik Gl. 1.21)(7.10)
AIR LAYER · EQ. 7.10

EQ. 7.10 WITH CURRENT VALUES

Unventilated air layers between ordinary surfaces (ε = 0.9), Rg in m²K/W (ISO 6946 Table 8; Bauphysik Tafel 2.2)
ThicknessHeat flow upHorizontalDown
5 mm0.110.110.11
10 mm0.150.150.15
15 mm0.160.170.17
25 mm0.160.180.19
50 mm0.160.180.21
100 mm0.160.180.22
300 mm0.160.180.23
07

PARALLEL PATHS · ISO 6946 LIMITS · ψ, χ · EQ. 7.11

Parallel paths and thermal bridges

Real walls are not homogeneous layers. Studs cross the insulation, slabs and balconies run through the facade, corners have more outside than inside surface. Heat takes the easy path, and that path is also where the inside surface is coldest.

parallel paths with area fractions fj (Σ fj = 1): conductances add, not resistancesU=∑jfj·Ujupper limit of R; ISO 6946 averages it with the lower limit of Figure 4(7.11)
Upper and lower limits of the thermal resistance of an inhomogeneous constructiona · upper limit R′T: adiabatic planesinoutEach section is its own wall; no heat crossesthe section boundaries. Sections add in parallel:1 / R′T = Σ f_j / R_T,j (overestimates R)b · lower limit R″T: isothermal planesinoutEach layer is averaged first; heat may movesideways into the stud. Layers add in series:R″T = R_si + Σ d_i / λ_mean,i + R_se (underestimates R)ISO 6946 uses R_T = (R′T + R″T) / 2, valid while R′T / R″T ≤ 1.5.Beyond that (steel studs, metal fixings) a numerical 2D or 3D calculation is required (ISO 10211).
Figure 4. Upper and lower limits for inhomogeneous layers (ISO 6946)Editable SVG ↓
STUD WALL · EQ. 7.11 · ISO 6946 §6.7

PARALLEL PATHS WITH CURRENT VALUES

Between 12.5 mm gypsum board and 12 mm OSB. Real frames add plates, noggings and headers: a framing fraction of 15–25 % is common.

Thermal bridge · Wärmebrücke
A local area with a higher heat flux than its surroundings, and therefore a lower inside surface temperature. "Cold bridge" (Kältebrücke) is a misnomer: heat flows out, cold does not flow in.
Material bridge
A better conductor crosses the insulation: steel and concrete through the facade, a balcony slab, a lintel, fixings, window frames.
Geometric bridge
The outer surface is larger than the inner one: corners, especially three-dimensional corners at the roof edge. Heat lines converge and the corner is the coldest point of a room.
ψ · W/(m·K) and χ · W/K
The extra heat flow per meter of a linear bridge (slab edge, window reveal) and per point bridge (a column, a bracket), calculated numerically (ISO 10211) or taken from catalogues (DIN 4108 Beiblatt 2). They add to the transmission heat loss: HT = Σ U·A + Σ ψ·l + Σ χ (Chapter 08, Eq. 8.2).
08

MATERIALS · EN PRODUCT STANDARDS · CARBON

Insulation materials

Insulation (λ < 0.1 W/(m·K)) traps gas in fibers or closed cells. They differ less in λ than in what else they do: carry load, tolerate water, burn or not, open or block vapor, store or emit carbon, and how they can be installed.

Insulation materials · typical design values · d for U = 0.20 W/(m²K) with R_si + R_se = 0.17 m²K/W and no other layers
MaterialProduct standardλ W/(m·K)ρ kg/m³c J/(kg·K)d for U 0.20Typical use
Mineral wool (rock, glass)MW · EN 131620.03530830169 mmCavities, roofs, ETICS, ventilated facades; non-combustible
Expanded polystyrene (EPS)EPS · EN 131630.035201210169 mmETICS, under screeds; cheap, combustible
Extruded polystyrene (XPS)XPS · EN 131640.030351210145 mmPerimeter and inverted roofs: wet ground, loads
Polyisocyanurate (PIR) boardPUR/PIR · EN 131650.023321400111 mmThin roof and wall build-ups; foil-faced boards
Wood-fiber boardWF · EN 131710.0421602100203 mmTimber frame, roofs; high c damps summer heat
Cellulose, blownLoose fill, ETA0.040502000193 mmBlown into frame cavities; recycled paper
Straw (compressed panel)ETA (e.g. EcoCocon)0.0521102000251 mmPrefabricated panels; stores biogenic carbon
Cork boardICB · EN 131700.0391201800188 mmETICS, floors; moisture tolerant
Cellular (foam) glassCG · EN 131670.0451201000217 mmUnder slabs and perimeter; load-bearing, vapor-tight
Mineral insulation board (AAC)Mineral board, ETA0.0451151300217 mmInterior insulation (e.g. Multipor); vapor-open
Aerogel blanketBlanket, ETA0.015150100072 mmRenovation where space is tight
Vacuum insulation panel (aged)ETA0.00719080034 mmVery thin build-ups; cannot be cut or pierced
09

HEAT STORAGE · TIME LAG · EQ. 7.12–7.13

Steady state and transient heat transfer

Outdoor temperature and sunshine change every hour, and walls store and release heat. Steady state ignores storage. That is exact when nothing changes and a good approximation over long periods. When it fails, density and specific heat enter the problem beside conductivity.

Temperature profiles in a concrete wall: steady state, after a step change and under a daily cyclea · steady stateinout300 mm concreteθ(x) fixed in timeq in = q out at every instant.Only λ and d matter (R, U).b · step: heating switched oninout300 mm concrete2 h12 h48 hsteadyHeat goes into storage first; the wall needsdays to settle (ρ, c and λ all matter).c · daily cycle outside ±10 Kinout300 mm concreteδ = 138 mmEnvelope of the daily swing; at depth δ theamplitude is 37 %, at 3δ only 5 %.
Figure 5. Steady state, a step change and a daily cycle in a concrete wallEditable SVG ↓
Steady state · stationär
Temperatures do not change with time; q is the same in every layer; λ and d decide everything. Over periods longer than about two weeks heat stored and released by the walls cancels out, so steady-state U-values give the seasonal heating demand reliably (Lehrbuch der Bauphysik II 2).
Transient · instationär
Temperatures change; part of the heat entering a layer is stored in it. How fast a temperature change travels into a material is set by its diffusivity α = λ/(ρc); how much heat a surface absorbs from a change by its effusivity b = √(λρc).
diffusivity and the penetration depth of a periodic temperature (period P)α=λρ·c,δ=α·Pπamplitude at depth x: e−x/δ, time lag: (x/δ) · P/2π (Incropera Eq. 5.69) m²/s, m(7.12)
Daily cycle (P = 24 h): diffusivity, penetration depth, effusivity and heat capacity
Materialα = λ/(ρc) · 10⁻⁷ m²/sδ (24 h)b = √(λρc) J/(m²K·s^½)ρ·c kJ/(m³K)Stored per K in the first δ
Concrete (stone mix)6.9138 mm16832024279 kJ/(m²K)
Brick, common4.5111 mm10741603178 kJ/(m²K)
Aerated concrete masonry (AAC)4.0105 mm37960063 kJ/(m²K)
Softwood (fir, pine)1.768 mm29170448 kJ/(m²K)
Wood-fiber board1.359 mm11933620 kJ/(m²K)
Mineral wool (rock, glass)14.1197 mm30255 kJ/(m²K)
Expanded polystyrene (EPS)14.5199 mm29245 kJ/(m²K)
Water (still)1.563 mm15974180265 kJ/(m²K)

A whole room responds with a time constant: its effective heat capacity C (J/K) divided by its heat loss coefficient H (W/K, Chapter 08). After a sudden change the room covers 63 % of the way to its new steady state in one τ.

time constant of a building or a zoneτ=CHthe lecture house (H = 258 W/K, 70 m² floor): light construction C ≈ 110 kJ/(m²K) × 70 m² → τ ≈ 8 h; heavy, 260 kJ/(m²K) → τ ≈ 20 h (ISO 13790 classes) s, h(7.13)

STEADY STATE IS ENOUGH FOR

  • U-values, code compliance (GEG in Germany, IECC / ASHRAE 90.1 in the US) and comparing constructions.
  • The design heat load on a cold, overcast winter night (Chapter 08).
  • Seasonal and annual heating demand in heating-dominated climates (degree-day and monthly methods).
  • Inside surface temperatures and the mold check at a design condition.

TRANSIENT IS CRITICAL FOR

  • Summer overheating and peak cooling loads: sun and internal gains peak for hours; mass shifts and damps the peak (time lag, decrement; TAV in German texts).
  • Night ventilation and passive cooling, which only work with accessible mass (lecture frames 572–574).
  • Intermittent heating: churches, schools, holiday homes. Light inner surfaces (small b) warm up fast; with a night setback heavy and light buildings save about the same (Bauphysik II 3.2).
  • Passive solar storage (Trombe walls, slabs in the sun) and how much solar gain can be used at all (Chapter 08, section 07).
  • Touch and floors: a concrete floor feels cold, cork warm, at the same temperature. Skin (b ≈ 1000) at 28 °C on concrete (b ≈ 2200) at 15 °C meets at 19 °C; on cork (b ≈ 100) at 27 °C.
10

9 QUESTIONS · CALCULATION AND CONCEPT

Self-test

"New values" generates a new variant of a calculation. Each answer shows a worked solution.

EDITABLE VECTOR FILES

Figure files

Editable SVG files of every figure. Interactive drawings save their current state with "Save SVG".

  1. heat-modes.svg · Fig. 1 · Conduction, convection and radiation in a wall section
  2. resistor-network.svg · Fig. 2 · Temperature profile and the equivalent resistor network (lecture example)
  3. air-cavity.svg · Fig. 3 · Air layers: conduction, convection cell and radiation
  4. iso6946-bounds.svg · Fig. 4 · Upper and lower limits for inhomogeneous layers (ISO 6946)
  5. steady-transient.svg · Fig. 5 · Steady state, a step change and a daily cycle in a concrete wall

SOURCES

Sources and model notes

  1. T. L. Bergman, A. S. Lavine, F. P. Incropera, D. P. DeWitt, Fundamentals of Heat and Mass Transfer, 6th ed., Wiley, 2007. §1.2–1.3, §3.1–3.2, §5.1–5.2, §5.9, §9.8, §12.4–12.7, §13.2; Tables 1.1, A.3, A.11, A.12.Rate equations (Eq. 7.2–7.5), composite walls, Biot number, periodic heating (Eq. 7.12), enclosures, emissivity and solar absorptivity.
  2. H.-M. Fischer, R. Jenisch, M. Stohrer et al., Lehrbuch der Bauphysik, 6th ed., Vieweg+Teubner, 2008. Part II Wärme: §1.4, §2.1–2.4, §3, §6–7, §8.3–8.5.ISO 7345 terms, surface and air-layer resistances, temperature profile and graphical method, effusivity and contact temperature, TAV, thermal bridges, fRsi.
  3. EN ISO 6946:2017, Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods (DIN EN ISO 6946).Rsi, Rse, Annex C surface coefficients, Annex D air layers (Eq. 7.10), upper and lower limits.
  4. DIN 4108-2:2013, Wärmeschutz und Energie-Einsparung in Gebäuden — Mindestanforderungen an den Wärmeschutz; DIN 4108-4 (design values); DIN 4108 Beiblatt 2 (thermal bridges).fRsi ≥ 0.70, design values of λ.
  5. ASHRAE, Handbook — Fundamentals, SI edition, Chapters 4 (heat transfer), 25–27 (heat, air and moisture; material properties; assembly U-factors).US surface films and design values; R-value conversion.
  6. EN ISO 10211 (thermal bridges, numerical), EN ISO 13788 (surface temperature to avoid mold), EN ISO 10456 (design values), EN ISO 13790 / EN ISO 52016-1 (heat capacity classes, hourly method).Section 07–09.
  7. S. V. Szokolay, Introduction to Architectural Science, 3rd ed., Routledge, 2014; N. Lechner, Heating, Cooling, Lighting, 4th ed., Wiley, 2015.Units, specific heat, the water analogy and the lecture examples.
  8. T. Dogan, ES1 lecture "Heat transfer, insulation materials", Cornell AAP, 2026, frames 516–636.Order of topics and the worked examples.
Model assumptions and precision

One-dimensional, steady conduction through plane, homogeneous layers with constant properties. Surface coefficients follow ISO 6946 Annex C with the inside at 20 °C and the outside at 10 °C; the radiation coefficient is linearized around that mean temperature. Air layers follow Annex D for large, unventilated cavities. The stud lab applies the ISO 6946 combined method; it does not replace a numerical calculation where R′T/R″T > 1.5. The dew point uses the Magnus formula (Sonntag constants); the mold limit is the surface temperature at which the room air reaches 80 % RH. Material values are typical design values; use product data and national tables for a real project. Section 09 uses a finite-difference solution for Figure 5 and the semi-infinite solution of Incropera Eq. 5.69 for the penetration depth.

Continue to Chapter 08: building heat balance ↗

ES1 / ENVIRONMENTAL SYSTEMS I Back to top ↑